Products
contact us
Yangzhou Ke Yu Electric Power Co., Ltd.
Address: No. 97, Zhongxin Road, Automobile Industrial Park, Yizheng City, Yangzhou City
Phone: 086-514-83900666
E-mali:keyudl09@126.com
Website: www.keyudl.com
KXGN-12 type user boundary switch cabinet
Summary
The KXGN - 12 type user demarcation switch cabinet equipment widely used in cables of rated voltage 12kV, rated frequency 50Hz tap, segmented, and multiple power point contact, applicable to the city underground cable ring and radiant power line and the control and the connection, and underground cables and overhead line hybrid net import line control and connection, realize the ring network power supply and radiation power. The product has the unique function of automatically removing branch line, grounding fault and interphase short circuit fault, which is called the function of dividing switch cabinet or watchdog function. It is a new high-tech product integrated with vacuum switch cabinet technology and microelectronic intelligent control technology.
Reference standard
GB/T11022 | Common technical requirements for high voltage switchgear and control equipment standards |
GB 3906 | 3.6kV ~ 40.5kV AC metal closed switch equipment and control equipment |
GB 1984 | High voltage AC circuit breaker |
GB 311.1 | Insulation coordination of high voltage transmission and transformation equipment |
GB/T3309 | Mechanical test of high voltage switchgear at normal temperature |
GB 4208 | Shell protection level (IP code) |
GB/T191 | Packaging, storage and transportation, illustrations |
DL/T404 | 3.6kV ~ 40.5kV AC metal closed switch equipment and control equipment |
Product model definition
technical parameter
Serial number |
project |
unit |
data |
||
1 |
Rated voltage |
kV |
12 |
||
2 |
Rated frequency |
Hz |
50 |
||
3 |
Power frequency withstand voltage |
Relatively, white and white |
kV/min |
42 |
|
Broken mouth |
kV/min |
48 |
|||
4 |
Lightning impulse withstand voltage (peak) |
Relatively, white and white |
kV |
75 |
|
Broken mouth |
kV |
85 |
|||
5 |
Rated current |
A |
630 |
||
6 |
Rated short-time withstand current |
kA |
20 (4s) |
||
7 |
Rated peak withstand current |
kA |
50 |
||
8 |
Rated short-circuit breaking current |
kA |
20 |
||
9 |
Rated short-circuit current |
kA |
50 |
||
10 |
Rated short-circuit breaking current frequency |
次 |
30 |
||
11 |
The number of mechanical life |
次 |
10000 |
||
12 |
Annual leakage rate |
/ |
≯1% |
||
13 |
Ambient air temperature |
The highest temperature |
℃ |
+70 |
|
14 |
Lowest temperature |
-40 |
|||
15 |
The maximum temperature difference |
K |
≤25 |
||
16 |
altitude |
m |
≤2000 |
||
17 |
humidity |
Daily average relative humidity |
% |
≤95 |
|
18 |
Monthly relative humidity average |
≤90 |
|||
19 |
Earthquake-resistant capacity |
Horizontal acceleration |
g |
0.3 |
|
20 |
Ground vertical acceleration |
0.15 |
|||
21 |
Safety factor |
/ |
6.7 |
Product model definition
typical application
1.Single switch multi-loop outdoor cable branch box
Into four out of the program Into four with a ring out (load switch) program
![]() |
use Generally used for outdoor cable tapping and cable-specific branch line monitoring. Can be protected branch of the single-phase control of the ground and short-circuit fault will not affect the trunk and adjacent lines; Can be configured as an integrated electric, can also be made into a full manual configuration, the maximum cable tap capacity into one into four. |
![]() |
Monitoring of specific branch lines of cables. Can protect the branch of the alleged single-phase ground fault and short-circuit fault will not affect the trunk and adjacent lines; Multi-circuit bus expansion. When the fixed cabinet type can not meet the requirements of the number of multi-circuit solutions in a single line, it can be used as an expansion cabinet type and realize the fault monitoring function. Upgrading of the existing lines, do not have the watchdog function of existing branch line into the switchgear, branch line monitoring. |
Cabinet size
1.Single switch multi-loop outdoor cable branch box (a switch)
2.Boundary switch cabinet internal dimensions
Products
Contact
Address: No. 97, Zhongxin Road, Automobile Industrial Park, Yizheng City, Yangzhou City
Phone: 0514-87520111
E-mali:kydl09@126.com
Website: www.keyudl.com




WeChat public account
copyright © 2017 Yangzhou Keyu Power 苏ICP备17049933号 Website construction: www.300.cn