SVR-12 solid insulation vacuum ring network cabinet (compact switch cabinet)
Category: Product Center
key word:
Hotline:
SVR-12 solid insulation vacuum ring network cabinet (compact switch cabinet)
Overview
This series of products integrates the switch unit and the primary diversion circuit through epoxy resin casting. Each ring main unit unit has three-phase phase units, which are connected by fully insulated busbars. All primary conductive parts are sealed together, especially SF6 gas.
The ring network cabinet can be configured with three-phase linkage permanent magnet mechanism or spring mechanism integrated intelligent control and protection unit, which can quickly cut off fault current and isolate faults. Smart grid requirements.
Suitable for substation 10kV outlet interval of power system, distribution switch station, user boundary ring network cabinet, user substation, ring network switch station, community, road, government department, hospital , petrochemical, metallurgy, mining, etc.
| ● IEC60298 | AC metal-enclosed switchgear and control equipment above 1kV and below 52kV |
| ● GB3906 | 3.6kV-40.5kV and below AC metal-enclosed switchgear and control equipment |
| ● CB/T 11022 | Common technical requirements for high voltage switchgear and controlgear standards |
| ● CL/T593 | Common technical requirements for high voltage switchgear and controlgear standards |
| ● CB1984 | High Voltage AC Circuit Breaker |
| ● GB1985 | High-voltage AC isolating switch and grounding switch |
| ● GB/T4208 | Enclosure rating (IP code) |
| ● DL/T721 | Distribution network automation system remote terminal |
| ● GB/T 17626 | Electromagnetic Compatibility Test and Measurement Technology |
| ● GB/T 14598 | Measurement of electrical disturbance test of relays and protective devices |
Model description

Technical parameters
Technical parameters of circuit breaker body
|
Project |
Parameters |
|
Rated voltage |
12kV |
|
Rated current |
630/1250V |
|
Rated (1min) power frequency withstand voltage (phase-to-phase and ground/fracture) |
42/48kV |
|
Rated lightning impulse withstand voltage (phase-to-phase and ground/fracture) |
75/85 |
|
Rated short-circuit breaking current |
20/25kA |
|
Rated short-circuit making current (peak) |
50/63kA |
|
Thermal stabilization current (4s) |
20/25kA |
|
Dynamic stable current (peak value) |
50/63kA |
|
Rated short-circuit current breaking times |
30 times |
|
Rated frequency |
50Hz |
|
Protection level |
IP4X |
|
Itinerary |
12±1mm |
|
Contact spacing |
9±1mm |
|
Overtravel |
3±1mm |
|
Close time |
30-50ms |
|
Opening time |
5-25ms |
|
Opening and closing at different periods |
≤2ms |
|
Close bounce |
≤2ms |
|
Average opening speed |
1.1±0.2m/s |
|
Average closing speed |
0.6±0.2m/s |
|
Mechanical life |
10,000 times |
|
Main circuit resistance (unit-unit) |
≤260μΩ |
Technical parameters of isolation/earthing switch
|
Project |
Parameters |
|
Rated voltage |
12kV |
|
Rated frequency |
50Hz |
|
Rated current |
630/1250A |
|
Rated 1min power frequency withstand voltage |
Isolation switch (phase-to-phase, phase-to-ground/fracture): 42/48kV |
|
Rated lightning impulse withstand voltage |
Isolation switch (phase-to-phase, phase-to-ground/fracture): 75/85kV |
|
Rated short-time withstand current |
20/25kA |
|
Rated Short Circuit Duration |
4s |
|
Rated peak withstand current |
50/63kA |
|
Mechanical life |
2000 times |
Use Environment
Ambient air temperature: -40℃~+70℃
Working environment humidity: 0-95%
Altitude of work place: ≤2000m
There is no obvious corrosive and flammable gas or smoke pollution in the surrounding air.
If the user cannot meet the above environmental conditions, please contact our company.
Technical Features
(1) Environmental protection, small size (width, depth and height 400 x 910 x 1620, only 1/4 of the volume of the traditional KYN28 cabinet, weight 200kg, only 1/2 of the traditional KYN28 cabinet) easy to install;
(2) Modular design is convenient for installation, debugging and maintenance;
(3) The unit structure is easy to expand and can be expanded infinitely;
(4) It is convenient to install the busbar on the top, and it is easy to expand;
(5) Reliability (mechanism, main circuit protection level P67);
(6) Safety (three-phase split, visible isolation fracture, grounding closure);
(7) Long life, maintenance-free (cooling and heating cycle, small partial discharge, airflow channel);
(8) The product can form a demarcation cabinet solution, with a cable-type watchdog function, to realize the user demarcation protection function, and to connect and protect the smart grid.