Product Brief
LW-12 outdoor pole-mounted SF6 circuit breaker is a new generation product developed by our company in response to the new requirements of the State Grid's primary and secondary integrated pole-mounted switches for network access. The switch configuration fully conforms to the State Grid's primary and secondary integration requirements. Procurement, mass production. The switch has compact structure, reasonable layout and complete functions. All indicators meet the requirements of the primary and secondary integration of the State Grid. The integrated CT, zero-sequence CT and zero-sequence voltage sensor with unified parameters are used for protection and measurement, with a wide measurement range and high measurement accuracy. , The characteristics of high reliability, complete analog quantity is convenient to accurately determine various faults of the line.
Product Composition
◆ LW-12 type common box type SF6 column circuit breaker, built-in 3-phase current transformer, zero-sequence current transformer and zero-sequence voltage sensor
◆ Intelligent feeder terminal (box type or hood type), built-in supporting power supply (battery or super capacitor), built-in line loss module (optional)
◆ Power voltage transformer (1 or 2 single-phase)
◆ Standard aerial plug and cable and installation accessories

It can be applied to the main line segment line, branch line dividing line and connecting line in my country's intelligent distribution network respectively.
Key Features
◆ SF6 arc-extinguishing structure, reliable for breaking short-circuit faults
◆ The distance between the ports is greater than 35mm, no external isolation knife switch is required, the isolation port has reliable insulation and strong anti-lightning impact ability
◆ One-step forming design of stainless steel shell is adopted to avoid stress deformation caused by secondary welding of finished products
◆ Large creepage distance and 250mm large phase-to-phase distance design, strong insulation ability, suitable for high altitude areas
◆ Quickly detect, discriminate and remove short-circuit current faults
◆ Remote control, telemetry, remote signaling, remote adjustment functions
◆ High-precision fault recording function
◆ Single-phase ground fault detection function
◆ Line damage detection and lean calculation
◆ Centralized and local feeder automation functions
◆ Strong electromagnetic compatibility and harsh environment adaptability
Main technical parameters
|
Serial number |
Name |
Units |
Parameter value |
|
|
1 |
SF6 circuit breaker |
|||
|
1.1 |
Model |
|
LW-12 |
|
|
1.2 |
Structure |
|
Total box type |
|
|
1.3 |
Arc extinguishing method |
|
SF6 |
|
|
1.4 |
Insulating medium |
|
SF6 |
|
|
1.5 |
Rated voltage |
kV |
12 |
|
|
1.6 |
Rated current |
A |
630 |
|
|
1.7 |
Rated power frequency 1min withstand voltage |
Relatively/Alternately |
kV |
42 |
|
|
|
Interface |
kV |
48 |
|
1.8 |
Rated lightning impulse withstand voltage (1.2∕50ms) peak value |
Relatively/Alternately |
kV |
75 |
|
|
|
Interface |
kV |
85 |
|
1.9 |
Rated short-time withstand current and duration |
kA/s |
20/4 |
|
|
1.10 |
Rated peak withstand current |
kA |
50 |
|
|
1.11 |
Rated short-circuit breaking current |
kA |
20 |
|
|
1.12 |
Rated short-circuit making current |
kA |
50 |
|
|
1.13 |
Mechanical stability |
times |
≥10000 |
|
|
1.14 |
Annual leakage rate of SF6 gas |
% |
≤0.05% |
|
|
1.15 |
Fracture distance |
mm |
≥35 |
|
|
1.16 |
Different periods of opening and closing |
ms |
≤2 |
|
|
1.17 |
Protection level of switch housing |
|
Not lower than IP67 |
|
|
1.18 |
Switch life |
Year |
Not less than 20 years |
|
|
2 |
Operating Organization |
|||
|
2.1 |
Type or model of operating mechanism |
|
Spring |
|
|
2.2 |
How to operate |
|
Electric, with manual operation function |
|
|
2.3 |
Motor voltage |
V |
DC24 |
|
|
3 |
Current transformers(built-in) |
|||
|
3.1 |
Rated current ratio |
|
Phase current: 600A/5A or 600A/1A |
|
|
3.2 |
Accuracy |
Grade |
Phase current: protection level 5P10, measurement level 0.5 |
|
|
3.3 |
Capacity |
VA |
Phase CT: ≥10VA at rated 5A, ≥1VA at rated 1A; |
|
|
3.4 |
Temperature range |
℃ |
-40℃~70℃ |
|
|
4 |
Zero-sequence voltage sensor (built-in) |
|||
|
4.1 |
Ratio |
|
(10kV/√3)/(6.5V/3) |
|
|
4.2 |
Accuracy |
Grade |
3P |
|
|
4.3 |
Partial discharge |
pC |
≤20(1.2Um/√3) |
|
|
4.4 |
Insulation resistance after combination with switch (switch to ground) |
MΩ |
>1000 |
|
|
5 |
Mains voltage transformer (external) |
|||
|
5.1 |
Quantity |
Only |
1 or 2 |
|
|
5.2 |
Rated voltage ratio |
|
Line voltage measurement: 10kV/0.1kV |
|
|
5.3 |
Accuracy |
Grade |
Phase voltage: level 0.5; supply voltage: level 3 |
|
|
5.4 |
Temperature range |
℃ |
-40℃~70℃ |
|
|
5.5 |
Partial discharge |
pC |
≤20(1.2Um/√3) |
|
|
5.6 |
Measure winding output capacity |
VA |
≥10VA |
|
|
5.7 |
Power winding output capacity |
VA |
≥300VA, short-term capacity≥500VA/1s |
|
|
6 |
Feeder Terminal (FTU) |
|||
|
6.1 |
Voltage input nominal value |
V |
Line Voltage: 100 |
|
|
6.2 |
Current input nominal value |
A |
Phase current: 5A or 1A |
|
|
6.3 |
Working power |
V |
AC220V, single or dual |
|
|
6.4 |
Switch measurement and control capacity |
|
|
|
|
6.5 |
Voltage measurement accuracy |
Grade |
Phase voltage: ≤0.5% (0.5 class) |
|
|
6.6 |
Current measurement accuracy |
Grade |
Phase measurement class 0.5 (≤1.2In), |
|
|
6.7 |
Accuracy of active power and reactive power |
|
≤1% (Level 1) |
|
|
6.8 |
Wireless Communication Module |
Communication system |
|
Support 4G/3G/2G five-mode self-adaptation, including: |
|
|
block |
Communication interface |
|
At least 2 RS232 serial ports, 9600bit/s; or 1 10/100M full-duplex Ethernet port. |
|
6.9 |
Line loss module (optional) |
Standard reference voltage |
V |
3×100V |
|
|
|
Standard reference current |
A |
1A, 5A |
|
|
|
Active energy accuracy |
Grade |
0.5S |
|
|
|
Reactive energy accuracy |
Grade |
2 |
|
6.10 |
Backup mode |
|
A: Maintenance-free VRLA battery |
|
|
|
|
|
B: Supercapacitor |
|
|
6.11 |
Structure |
|
Box or hood |
|
|
6.12 |
Protection level |
|
Not lower than IP67 |
|
|
6.13 |
Ambient temperature |
℃ |
-40℃~+70℃ |
|
|
7 |
One and two fusion sets |
|||
|
7.1 |
Fault trip |
|
Realize single-phase grounding and phase-to-phase short-circuit fault processing, and can directly trip to remove faults. |
|
|
7.2 |
Fault Clearance Time |
|
The whole group action time of phase-to-phase fault is not more than 100ms |
|
|
7.3 |
Feeder automation |
|
Support centralized feeder automation |
|
Dimensions

Professional test report of primary and secondary fusion complete sets of circuit breakers

Related products
Product message
Contact
Address: No. 97, Zhongxin Road, Automobile Industrial Park, Yizheng City, Yangzhou City
Phone: 0514-83900666
E-mali:kydl09@126.com
Website: www.keyudl.com
Mobile website
Copyright:Yangzhou Keyu Power Co., Ltd.