KW32-12 household high voltage intelligent spring air circuit breaker
Category: Product Center
key word:
Hotline:
KW32-12 household high voltage intelligent spring air circuit breaker
Overview
KW32-12 outdoor high-voltage intelligent spring vacuum circuit breaker is a three-phase AC circuit breaker with a rated voltage of 12kV and a frequency of 50Hz. This product is an intelligent spring mechanism vacuum circuit breaker independently developed by our company. It is suitable for switching various loads of different natures and occasions of frequent operation, and has the ability to break short-circuit current many times. It is suitable for protection and control in the power distribution system of substations and industrial and mining enterprises. Retrofit.
Citation Standards
| GB1984 GB/T 11022 GB/T 311.1 GB/T 3309 DL/T 593 DL/T 402 |
AC high voltage circuit breaker Common technical requirements for high voltage switchgear and controlgear standards Insulation coordination of high voltage power transmission and transformation equipment Mechanical test of high voltage switchgear at normal temperature Technical Guidelines for Common Ordering of High Voltage Switchgear Ordering technical conditions of AC high voltage vacuum circuit breaker |
Ambient conditions used
◆Working environment temperature: -40~+70℃
◆Working environment humidity: 0~95%
◆Work site altitude: ≤3000 m
◆Wind pressure: ≤ 700 Pa
◆Icing thickness: ≤10mm
◆Outer insulation pollution level: Ⅳ
◆Earthquake intensity: ≤ 8 degrees
Note: This product is not suitable for places such as fire, explosion hazard, chemical corrosion and severe vibration.
Model description
Product model and meaning:

Features
◆Using three-phase strut structure, vacuum arc extinguishing, reliable breaking, small contact wear, maintenance-free;
◆Epoxy resin and silicone rubber composite insulation material, good pressure and weather resistance, no oil, no SF6, environmental protection and no pollution;
◆The operating mechanism adopts a miniaturized spring operating mechanism, the power of the energy storage motor is small, the energy consumption of opening and closing is low, and the reliability is high;
◆It can be equipped with an integrated isolation knife switch, with obvious visual disconnection point and anti-mistake interlocking device.
Dimensional drawing

Ontology technical parameters
Circuit breaker switch technical parameters
|
Serial number |
Name Name |
Units |
Parameter Number |
|
1 |
Rated voltage |
kV |
12 |
|
2 |
Rated current |
A |
630/1250 |
|
3 |
Rated frequency |
Hz |
50 |
|
4 |
Rated lightning impulse withstand voltage |
kV |
Ground 75/Fracture 85 |
|
5 |
Rated short-term power frequency withstand voltage (1min) |
kV |
Wet test 34, dry test 42/fracture 48 |
|
6 |
Rated short-circuit breaking current |
kA |
20/25 |
|
7 |
Rated short-circuit breaking times |
times |
30 |
|
8 |
Rated thermal stability current (4s) |
kA |
20/25 |
|
9 |
Rated dynamic stable current |
kA |
50/63 |
|
10 |
Rated short-circuit making current |
kA |
50/63 |
|
11 |
Mechanical life |
times |
30000 |
|
12 |
Secondary circuit power frequency withstand voltage (1min) |
KV |
2 |
|
13 |
Nominal operating sequence |
|
O-0.3S-CO-180S-CO |
|
14 |
Net weight |
KG |
100 |
Mechanical parameters
|
Serial number |
Name Name |
Units |
Ref Number |
|
1 |
Itinerary |
mm |
11±1 |
|
2 |
Contact Spacing |
mm |
9±1 |
|
3 |
Overtravel |
mm |
3±1 |
|
4 |
Close time |
ms |
≤60 |
|
5 |
Opening time |
ms |
≤60 |
|
6 |
Open and close different periods |
ms |
≤2 |
|
7 |
Close bounce |
mm |
≤2 |
|
8 |
Average opening speed |
m/s |
1.0±0.2 |
|
9 |
Average closing speed |
m/s |
0.6±0.2 |
|
10 |
Mechanical times |
times |
30000 |
|
11 |
Main circuit resistance |
μΩ |
≤80 |
|
12 |
Main circuit resistance (with isolation switch) |
μΩ |
≤ 180 |
Feature introduction
Telemetry function: It can detect AC analog quantities such as voltage and current, and DC analog quantities such as battery voltage and temperature.
Remote signaling function: It can detect status information such as switch status signal, switch energy storage signal, battery low voltage alarm, etc., and has dual-position remote signaling processing function to support remote signaling displacement priority transmission.
Remote control function: radio frequency wireless remote control opening and closing. Equipped with a local/remote selection switch, which can be connected to the master station to remotely control the opening and closing.
Fault detection function: configure single-phase grounding, three-stage phase-to-phase protection, overload, anti-inrush current protection and other protection functions, and record the protection current.
Communication function: with serial port and network communication interface, built-in 101, 104 and other power industry standard communication protocols, can upload data to the master station through optical fiber/Ethernet, GPRS/CDMA, etc.
Self-diagnosis and self-recovery function: with self-diagnosis function, when internal software and hardware abnormalities are found, they can be recorded and reported in time, and the software has the function of self-recovery after power-on.
Power management function: support dual-channel AC backup power supply, use battery as backup power supply, and use soft switching technology to cut in seamlessly. When the main power supply fails, the backup power supply can be automatically and seamlessly switched on; it has the function of battery activation management, which can be realized automatically and manually Charge and discharge the battery.
Technical parameters of control box
|
Features |
Metrics |
Number and details of function points |
|
Current sampling |
5A/1A |
4 (3-way phase current 1-way zero sequence current) |
|
Voltage sampling |
AC220V/AC100V |
4 (2 line voltage or 3 line phase voltage 1 line zero sequence voltage) |
|
remote input |
empty node |
7 (7-way opening, such as opening and closing position, energy storage position, etc.) |
|
Communication input |
AC165~265V |
1 (normal configuration 1-way can be configured with 2-way automatic switching if required) |
|
align switch |
Flick switch |
Opening and closing energy storage DC24V 300W |
|
align switch |
Permanent magnet switch |
Coil DC220V40A |
|
Communication protocol |
IEC101 Balanced, Unbalanced IEC104 DNP3.0 ModBus |
|
Control box performance parameters
| feature |
Units |
Metrics |
|
AC current loop overload capacity |
|
2In, continuous work; 10In, 10s; 20In, 1s |
|
AC voltage loop overload capacity |
|
1.5Un continuous work |
|
Remote Signaling Resolution |
ms |
≤2ms |
|
Software anti-shake time |
ms |
0~6000ms can be set |
|
Device Power Consumption |
w |
≤15w |
|
Measurement accuracy |
% |
Voltage, current 0.5 %, active power, reactive power 1.0 % |
|
Backup power |
|
Maintain normal operation for more than 8 hours after AC power failure |
|
Controlling output node capacity |
|
DC24V/16A, AC250V/10A |
|
Insulation Properties |
MΩ |
≥5MΩ |
|
EMC |
|
IV |
|
Protection level |
IP |
IP54 |
|
Ambient temperature |
|
-40℃~+70℃, the maximum temperature change rate, 1.0℃/min |
|
Ambient humidity |
|
Relative humidity 10~100 %, maximum absolute humidity, 35g/㎥ |
Control Box Dimensions

Related products
Product message
Contact
Address: No. 97, Zhongxin Road, Automobile Industrial Park, Yizheng City, Yangzhou City
Phone: 0514-83900666
E-mali:kydl09@126.com
Website: www.keyudl.com
Mobile website
Copyright:Yangzhou Keyu Power Co., Ltd.