FKW28-12 outdoor intelligent vacuum load switch
Category: Product Center
key word:
Hotline:
FKW28-12 outdoor intelligent vacuum load switch
Overview
FKW28-12 outdoor intelligent vacuum load switch is a new generation of load switch for 10kV overhead power distribution system, with manual and electric operation functions. The switch adopts vacuum arc extinguishing, zero gauge pressure SF6 gas external insulation, no possibility of gas leakage, high reliability and maintenance-free.
FKW28-12 vacuum load switch can be widely used in the construction and renovation of 10kV overhead lines in urban distribution networks and 10kV power supply lines in rural power grids. Such as supporting the distribution network automation remote terminal, it can cooperate to realize the user demarcation function.
Citation Standards
| GB3804 | 3.6kV-40.5kV high voltage AC load switch |
| GB/T 11022 | Common technical requirements for high voltage switchgear and controlgear standards |
| GB/T 311.1 | Insulation coordination of high voltage power transmission and transformation equipment |
| GB/T 3309 | Mechanical test of high voltage switchgear at room temperature |
| DL/T 593 | Technical Guidelines for Common Ordering of High Voltage Switchgear |
| DL/T 402 | Technical conditions for ordering AC high voltage vacuum circuit breakers |
Environmental conditions used
| ◆Ambient temperature: | 40~+70℃ |
| ◆Working environment humidity: | 0~95% |
| ◆Work Location Elevation: | ≤3000 m |
| wind pressure: | ≤ 700 Pa |
| ◆Ice Thickness: | ≤10mm |
| ◆Outer insulation pollution level: | Ⅳ |
| ◆Seismic Intensity: | ≤ 8 degrees |
Note: This product is not suitable for places such as fire, explosion hazard, chemical corrosion and severe vibration.
Model description
Product model and meaning:

Technical parameters
|
Serial number |
Name Name |
Units |
Parameter Number |
|
1 |
Rated voltage |
kV |
12 |
|
2 |
Rated current |
A |
630 |
|
3 |
Rated frequency |
Hz |
50 |
|
4 |
Rated lightning impulse withstand voltage |
kV |
Ground 75/Fracture 85 |
|
5 |
Rated short-term power frequency withstand voltage (1min) |
kV |
Wet test 34, dry test 42/fracture 48 |
|
6 |
Rated thermal stability current (4s) |
kA |
20 |
|
7 |
Rated dynamic stable current |
kA |
50 |
|
8 |
Rated short-circuit making current |
kA |
50 |
|
11 |
Mechanical life |
times |
10000 |
|
12 |
Secondary circuit power frequency withstand voltage (1min) |
kV |
2 |
|
13 |
Nominal operating sequence |
|
O-0.3S-CO-180S-CO |
|
14 |
Net weight |
KG |
≤180 |
Dimensional drawing

Related products
Product message
Contact
Address: No. 97, Zhongxin Road, Automobile Industrial Park, Yizheng City, Yangzhou City
Phone: 0514-83900666
E-mali:kydl09@126.com
Website: www.keyudl.com
Mobile website
Copyright:Yangzhou Keyu Power Co., Ltd.